Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series

Revision May 2009, 00DE, V0.50

6-7

Fault

Name

Fault Descriptions

Corrective Actions

Keypad communication
time-out

1.

Check if the wiring for the communication is

correct.

2.

Check if there is any wrong with the keypad.

6.1.2 Reset

There are three methods to reset the brushless DC motor drive after solving the fault:

1.

Press STOP/RESET key on keypad.

2.

Set external terminal to “RESET” and then set to be ON.

3.

Send “RESET” command by communication.

NOTE

Make sure that RUN command or signal is OFF before executing RESET to prevent damage or

personal injury due to immediate operation.

6.2 Maintenance and Inspections

Before the check-up, always turn off the power and remove the cover. Wait at least 10 minutes after

all display lamps have gone out, and then confirm that the capacitors have fully discharged by

measuring the voltage between

~

. It should be less than 25VDC.

Ambient environment

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

Check the ambient temperature,
humidity, vibration and see if
there are any dust, gas, oil or
water drops

Visual inspection and measurement
with equipment with standard
specification

{

Check if there are any
dangerous objects in the
environment

Visual inspection

{