Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series

4-68

Revision May 2009, 00DE, V0.50

The parameter is set by the output frequency, current and operation time of the drive for

activating the I

2

t electronic thermal protection function. The function will be activated for the

150% * setting current for the setting of Pr.06-13

1

2

3

4

5

60Hz

0

50

100

150

200

Operation
time(min)

Load
fac tor (% )

06-14

Heat Sink Over-heat (OH) Warning

Control

mode

VF

VFPG

FOCPM

Factory setting: 85.0

Settings

0.0 to 110.0

o

C

06-15

Stall Prevention Limit Level

Control

mode

VF

VFPG

FOCPM

Factory setting: 50

Settings

0 to 100% (refer to Pr.06-02, Pr.06-03)

When the operating frequency is larger than Pr.01-01, Pr06-02=150%, Pr. 06-03=100% and

Pr. 06-15=80%:

Stall Prevention Level during acceleration = 06-02x06-15=150x80%=120%.

Stall Prevention Level at constant speed= 06-03x06-15=100x80%=80%.

06-02

06-15

01-01

01-01

x06-02

Stall Prevention Level

output frequency

frequency