Maximum Torque Command

Control

mode

FOCPM

Factory Setting: 100

Settings

0

to

300%

This parameter is for the max. torque command (motor rated torque is 100%).

07-15

Reserved

07-16

Reserved

07-17

Reserved

07-18

Reserved

07-19

Source of Torque Offset

Control

mode

FOCPM

Factory Setting: 0

Settings

0

Disable

1

Analog input (Pr.03-00)

2

Torque offset setting (Pr.07-20)

3

Control by external terminal (by Pr.07-21 to Pr.07-23)

This parameter is the source of torque offset.

When it is set to 3, the source of torque offset will decide to Pr.07-21, Pr.07-22 and Pr.07-23

by the multi-function input terminals setting (31, 32 or 33).

02-01~02-08 is set to 31 02-01~02-08 is set to 32 02-01~02-08 is set to 33

Torque offset

OFF OFF OFF None
OFF OFF ON 07-23
OFF ON OFF

07-22

OFF ON ON

07-23+07-22

ON OFF OFF

07-21

ON OFF ON

07-21+07-23

ON ON OFF

07-21+07-22

ON ON ON

07-21+07-22+07-23

07-20

Torque Offset Setting

Control

mode

FOCPM

Factory Setting: 0.0

Settings

0.0 to 100.0%

This parameter is torque offset. The motor rated torque is 100%.

07-21

High Torque Offset

Control

mode

FOCPM

Factory Setting: 30.0

Settings

0.0 to 100.0%