It is used to set the accel./decel. time selection when stall prevention occurs at constant

speed.

06-05

Over-torque Detection Selection (OT1)

Control

mode

VF

VFPG

FOCPM

Factory setting: 0

Settings

0

Over-Torque detection disabled.

1

Over-torque detection during constant speed operation, continue to
operate after detection

2

Over-torque detection during constant speed operation, stop
operation after detection

3

Over-torque detection during operation, continue to operate after
detection

4

Over-torque detection during operation, stop operation after
detection

06-06

Over-torque Detection Level (OT1)

Control

mode

VF

VFPG

FOCPM

Factory setting: 150

Settings

10

to

250%

06-07

Over-torque Detection Time (OT1)

Control

mode

VF

VFPG

FOCPM

Factory setting: 0.1

Settings

0.0 to 60.0 sec

06-08

Over-torque Detection Selection (OT2)

Control

mode

VF

VFPG

FOCPM

Factory setting: 0

Settings

0

Over-Torque detection disabled.

1

Over-torque detection during constant speed operation, continue to
operate after detection

2

Over-torque detection during constant speed operation, stop
operation after detection

3

Over-torque detection during operation, continue to operate after
detection

4

Over-torque detection during operation, stop operation after
detection

06-09

Over-torque Detection Level (OT2)

Control

mode

VF

VFPG

FOCPM

Factory setting: 150

Settings

10

to

250%