Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-91

‘0’

Exception code

‘2’

‘7’

LRC CHK Low

LRC CHK High

‘7’

CR

END 1
END 0

LF

The explanation of exception codes:

Exception

code

Explanation

01

Illegal function code:
The function code received in the command message is not
available for the brushless DC motor drive.

02

Illegal data address:
The data address received in the command message is not
available for the brushless DC motor drive.

03

Illegal data value:
The data value received in the command message is not available
for the brushless DC motor drive.

04

Slave device failure:
The brushless DC motor drive is unable to perform the requested
action.

10

Communication time-out:
If Pr.09-03 is not equal to 0.0, Pr.09-02=0~1, and there is no
communication on the bus during the Time Out detection period (set
by Pr.09-03), “cE10” will be shown on the keypad.

09-05

Response Delay Time

Control

mode

VF

VFPG

FOCPM

Factory Setting: 2.0

Settings

0.0 ~ 200.0 ms

This parameter is the response delay time after AC drive receives communication command

as shown in the following.

PC or PLC command

Handling time
of the AC drive

Response Delay Time

Response Message
of the AC Drive

RS-485 BUS