Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-39

temperature, carrier frequency will be lowered to 10kHz, moreover, overload condition will be adjust,

e.g. Fc= 15kHz, rated output current= 50% * 55% = 82.5% and continues for 1 minute, the carrier

frequency (Fc) will be reduced to the default setting.

O

verload Adjusting Graph

The control of maximum running speed differ upon PWM setting, therefore, carrier frequency

setting must be 27 times greater than the actual outputted frequency to attain best speed

control response.

For example, if Pr.00-12 setting is 2K, in order to attain best rotation speed control response,

the max. output frequency must be less than 74.07Hz. When number of motor poles is 5

, t

he

rotation speed is controlled to around 888rpm; in this case, it is recommend to set carrier

frequency to 2K and speed command to 900rpm. When carrier frequency (Pr. 00-12) setting

is 6K or lower, please refer to the following chart for value of carrier frequency and rotation

speed: