Delta BLD-E1 brushless DC motor drive BLD-E1 Series User Manual
Page 84
Chapter 4 Parameters| BLD-E1 Series
Revision May 2009, 00DE, V0.50
4-43
01-03
2nd Output Frequency Setting
Control
mode
VF
VFPG
Factory setting: 0.50
Settings
0.00~400.00Hz
01-04
2nd Output Voltage Setting
Control
mode
VF
VFPG
Settings
230V series
0.1 to 255.0V
Factory Setting: 5.0
460V series
0.1 to 510.0V
Factory Setting: 10.0
01-05
3rd Output Frequency Setting
Control
mode
VF
VFPG
Factory setting: 0.50
Settings
0.00~400.00Hz
01-06
3rd Output Voltage Setting
Control
mode
VF
VFPG
Settings
230V series
0.1 to 255.0V
Factory Setting: 5.0
460V series
0.1 to 510.0V
Factory Setting: 10.0
01-07
4th Output Frequency Setting
Control
mode
VF
VFPG
Settings
0.00~400.00Hz
Factory Setting: 0
01-08
4th Output Voltage Setting
Control
mode
VF
VFPG
Settings
230V series
0.1 to 255.0V
Factory Setting: 0.0
460V series
0.1 to 510.0V
Factory Setting: 0.0
V/f curve setting is usually set by the motor’s allowable loading characteristics. Pay special
attention to the motor’s heat dissipation, dynamic balance, and bearing lubricity, if the loading
characteristics exceed the loading limit of the motor.
For the V/f curve setting, it should be Pr.01-01
≥ Pr.01-03≥ Pr.01-05≥ Pr.01-07. There is no
limit for the voltage setting, but a high voltage at the low frequency may cause motor damage,
overheat, stall prevention or over-current protection. Therefore, please use the low voltage at
the low frequency to prevent motor damage.
V/F curve would only function as Pr. 00-09= 0 or 1 (under V/F control mode) and Pr. 00-10=0.