Dip switch s3/5, Dip switch s3/6 – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual
Page 93

Operating Instructions – MOVIMOT® MM03C - MM3XC
93
8
Description of the DIP switches S3
Startup with Integrated AS-Interface
DIP switch S3/5
Motor type
With IEC and NEMA motors, DIP switch S3/5 must always be set to OFF, for Brazilian
motors to ON.
DIP switch S3/6
Releasing the brake without enable
With activated switch S3/6 = "ON", the brake can also be released if no drive enable is
present.
Operation with
braking resistor
The special function is not in effect if operated with braking resistor.
Releasing the
brake
The brake can be released under the following conditions by setting the AS-i bit "speed
f1/speed f2":
Setpoint selection
Setpoint selection dependent on AS-i bit "speed f1/speed f2":
Behavior with a
non-operating unit
In case of a non-operating unit, the brake is always applied independent of the setting
of AS-i bit "speed f1/speed f2".
LED display
The yellow LED display flashes periodically and quickly (t
on
: t
off
= 100 ms : 300 ms) if
the brake was released for manual procedure.
Status of
AS-i bit
Enable condition
Fault condi-
tion
Brake function
D0
(R)
D1
(L)
D2
(f1/f2)
"1"
"0"
"0"
"1"
"0"
Unit enabled
No
Unit fault
Brake is controlled by MOVIMOT
®
,
setpoint f1
"1"
"0"
"0"
"1"
"1"
Unit enabled
No
Unit fault
Brake is controlled by MOVIMOT
®
,
setpoint f2
"1"
"0"
"1"
"0"
"0"
Unit not
enabled
No
Unit fault
Brake closed
"1"
"1"
"1"
Unit not
enabled
No
Unit fault
Brake closed
"0"
"0"
"1"
Unit not
enabled
No
Unit fault
Brake released for manual procedure
All conditions possi-
ble
Unit not
enabled
Unit fault
Brake closed
Bit D3 (Reset/Controller enable) must be set to enable the drive.
Enable condition
AS-i bit
Active setpoint
Unit enabled
D2 = "0"
Setpoint potentiometer f1 active
Unit enabled
D2 = "1"
Setpoint potentiometer f2 active
0
0
I