Operating Instructions – MOVIMOT® MM03C - MM3XC
10
Diagnostics of MOVIMOT® standard design
Diagnostics
Diagnostics via
MDG11A option
•
The diagnostic unit cannot be used in conjunction with MOVIMOT
®
with integrated
AS-Interface.
•
The diagnostic unit must be connected prior to the possible occurrence of a fault, as
MOVIMOT
®
error messages are not saved and the information is lost when the 24 V
supply is disconnected.
•
The diagnostic unit may only be connected to a MOVIMOT
®
unit.
•
Connecting the MDG11A to an RS-485 bus with several MOVIMOT
®
is not allowed.
•
The diagnostic unit can be used only if the MOVIMOT
®
is controlled via terminals.
This requires that DIP switches S1/1 to S1/4 are set to OFF (= address 0).
•
Do nut use the diagnostic unit in case setpoint setting takes place via the
RS-485 interface.
•
Connection according to section "Electrical Installation."