Dip switches s2/3, Dip switches s2/4, Dip switches s2/5 to s2/8 – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual
Page 57
![background image](/manuals/646387/57/background.png)
Operating Instructions – MOVIMOT® MM03C - MM3XC
57
7
Description of the DIP switches S2
Startup of Standard Design
DIP switches
S2/3
Control process
•
DIP switches S2/3 = OFF:
VFC operation for 4-pole motors
•
DIP switches S2/3 = ON:
U/f operation reserved for special cases
DIP switches
S2/4
Speed monitoring
•
Speed monitoring (S2/4 = "ON" is used for the protection of the drive during blocking.
•
If the drive is operated at the current limit for more than 1 second with active speed
monitoring (S2/4 = "ON"), the speed monitoring trips. MOVIMOT
®
signals a fault via
status LED (red, flashing slowly, fault code 08). The current limit must be attained un-
interruptedly for the duration of the delay time before the monitoring function re-
sponds.
DIP switches
S2/5 to S2/8
Selection of options
•
Special functions can be selected using the binary coding of the DIP switches.
•
The possible values can be set as follows:
•
An overview of the selectable special functions can be found on page 58.