Process output data – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual
Page 120
120
Operating Instructions – MOVIMOT® MM03C - MM3XC
9
Coding of process data
Startup with Communications Interface / Fieldbus
Process output
data
Process output data are sent from the master controller to the MOVIMOT
®
inverter (con-
trol information and setpoints). However, they only come into effect in MOVIMOT
®
if the
RS-485 address in MOVIMOT
®
(DIP switches S1/1 to S1/4) is set to a value other than
0. MOVIMOT
®
can be controlled with the following process output data:
•
PO1: Control word
•
PO2: Speed [%] (setpoint)
•
PO3: Ramp
Control word, bits
0...2
The "Enable" control command is specified with bits 0...2 by entering the control word =
0006
hex
. The CW and/or CCW input terminal must also be set to +24 V (jumpered) to
enable the MOVIMOT
®
unit.
The "Stop" control command is issued by resetting bit 2 = "0." You should use the stop
command 0002
hex
to ensure compatibility with other SEW inverter products. However,
MOVIMOT
®
always triggers a stop with the current ramp whenever bit 2 = "0," irrespec-
tive of the status of bit 0 and bit 1.
Control word bit 6
= Reset
In the event of a malfunction, the fault can be acknowledged with bit 6 = "1" (Reset). The
value of unassigned control bits should be 0 to ensure compatibility.
Speed [%]
The speed setpoint is specified as a percentage value in reference to the maximum
speed set with the f1 setpoint potentiometer.
Coding:
C000
hex
= -100 % (counterclockwise rotation)
4000
hex
= +100 % (clockwise rotation)
→
1 digit = 0,0061 %
Example:
80 % f
max
, CCW rotation:
Calculation:
–80 % / 0.0061 = –13115
dec
= CCC5
hex
Ramp
If the process data exchange takes place using three process data words, the current
integrator ramp is transmitted in process output data word PO3 . The integrator ramp set
with switch t1 is used if MOVIMOT
®
is controlled by two process data.
Coding:
1 digit = 1 ms
Range:
100...10000 ms
Example:
2.0 s = 2000 ms = 2000
dec
= 07D0
hex
Basic control block
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
PO1: Control word
reserved for special functions = "0"
"1" =
Reset
reserved = "0"
"1 1 0" = Release
otherwise stop
PO2: Setpoint
Signed percentage / 0.0061 %
Example: -80% / 0.0061 % = - 13115 = CCC5
hex
PO3: Ramp (only for
three-word protocol
only)
Time from 0 to 50 Hz in ms (range: 100...10000 ms)
Example: 0.2 s = 2000 ms = 07DO
hex
0
0
I