beautypg.com

Metalfab SEW Eurodrive MOVIMOT MM..C User Manual

Page 75

background image

Operating Instructions – MOVIMOT® MM03C - MM3XC

75

7

Selectable special functions MM..C-503-00

Startup of Standard Design

Use of relay out-
put with special
functions 7, 9 and
12

The following figure shows the use of relay contact K1 to control the mechanical brake
with brake rectifier BGM.

Important: Please observe the following before startup with brake control BGM:

The brake coil must correspond to the supply voltage (e.g. 400 V).

Special function 7, 9 or 12 must be activated, otherwise the brake is perma-
nently released. This must also be observed in the case of an exchange of the
MOVIMOT

®

inverter.

If neither of the listed functions is activated, relay contact K1 functions as ready sig-
nal contact. This means that the brake will be released without enable if the
BGM is used, if it was connected without permission.

52121AXX

[1] Brake control BGM installed in the terminal box
[2] External braking resistor BW (see the "Technical Data" section for the assignment)
[3] 24 V

DC

supply

[4] CW/Stop
[5] CCW/Stop

Observe the enabled direction of rotation (see the section "Connection of MOVIMOT® Basic
Unit" functions of CW/ Stop, CCW/Stop terminals with control via RS-485 interface)

[6] Setpoint toggle f1/f2
[7] Brake relays

M

3~

L1
L2
L3
PE

K11

F11/F12/F13

K1

RS-485

13

RD

RD

BK
BK

WH

BU

BU

14

15

L3

24V

R

L

f1/f2

K1a

K1b

RS-

RS+

=

+

-

MOVIMOT

+

~
~

[1]

[2]

[3]

[4] [5][6] [7]

BMG

BGM

MOVIMOT

24 V

DC

13

14

15

L1

L2

_

U

IN

U

E

0

0

I