Operating Instructions – MOVIMOT® MM03C - MM3XC
131
10
Diagnostics of MOVIMOT® standard design
Diagnostics
Diagnostics proce-
dure
The diagnostic unit can display different information such as operating status, motor cur-
rent, status of input terminals, status of message relay and brake. The selection is made
by pressing the button
. If a fault occurs, the fault number is automatically displayed.
Motor cur-
rent
Brake
Relay
Terminal R
Terminal L
Terminal f1/f2
Operational status
05623AXX
Display
Message
Operational status
---
No communication no 24 V at MOVIMOT
®
or RS-485 connection is incorrect (interrupted or
switched cable)
c 0
Not ready supply voltage is missing, but 24 V are present
c 2
Ready for operation supply voltage and 24 V are present, but no enable signal at terminal R or L
c 4
Enabled with motor rotating
Fault codes
F01
Short circuit of inverter output
F06
Mains phase fault
F07
DC link voltage too high
F11
Thermal overload of the output stage
F84
Thermal overload of the motor or motor blocked
F89
Thermal overload of the brake or internal resistance of the brake not correct
F90
Assignment motor–inverter incorrect (e.g. MM03 – DT71D4
Ħ
)
Motor current
0...180
Displays percentage of inverter nominal current, from 0% to 180%
Brake
o10
Brake applied
o11
Brake released
Relay
o20
Inverter not ready for operation (supply voltage is missing or inverter is in "fault" condition, see
Operating States or Fault Codes)
o21
Inverter ready
Terminal R
i10
Terminal R = "0"
i11
Terminal R = "1" = CW rotation
Terminal L
i20
Terminal L = "0"
i21
Terminal L = "1" = CCW rotation
Terminal f1/f2
i30
Terminal f1/f2 = "0" = Setpoint f1 active
i31
Terminal f1/f2 = "1" = Setpoint f2 active
c _
_ _ _
o 1 _
o 2 _
i 1 _
i 2 _
i 3 _