7 startup of standard design, 1 important startup instructions, 2 description of the controls – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual
Page 51: Setpoint potentiometer f1, Setpoint switch f2, Switch t1, Startup of standard design 7.1, Important startup instructions, Description of the controls, 7startup of standard design
Operating Instructions – MOVIMOT® MM03C - MM3XC
51
7
Important startup instructions
Startup of Standard Design
7
Startup of Standard Design
7.1
Important startup instructions
•
It is essential to comply with the safety notes during installation!
•
Before removing/attaching the MOVIMOT
®
inverter, it must be disconnected
from the power supply system (mains). Dangerous voltages may still be
present for up to 1 minute after shutdown.
•
Ensure before startup that the drive has not been damaged.
•
Check that all protective covers are installed correctly.
•
Use "CW/Stop" or "CCW/Stop" for jog mode.
•
A minimum switch-off time of 2 seconds must be maintained for the mains contactor
K11.
7.2
Description of the controls
Setpoint potenti-
ometer f1
The potentiometer has a different function, depending on the unit operating mode:
•
Control via terminals:
Setpoint f1 (selected by tl. f1/f2 = "0")
•
Control via RS-485:
Maximum frequency f
max
Setpoint switch f2
The function of the switch changes depending on the unit operating mode:
•
Control via terminals:
Setpoint f2 (selected by tl. f1/f2 = "1")
•
Control via RS-485:
Minimum frequency f
min
Switch t1
For integrator ramp (ramp times based on a setpoint jump of 50 Hz)
05066BXX
[1] Pot. position
1
2
3
4
5
6
7
8
9
10
0
100
f [Hz
[1]
]
2
75
25
50
6
5
f
1
Switch f2
Detent position
0
1
2
3
4
5
6
7
8
9
10
Setpoint f2 [Hz]
5
7
10
15
20
25
35
50
60
70
100
Mini. frequency [Hz]
2
5
7
10
12
15
20
25
30
35
40
3
4
5
6
7
8
Switch t1
Detent position
0
1
2
3
4
5
6
7
8
9
10
Ramp time t1 [s]
0.1
0.2
0.3
0.5
0.7
1
2
3
5
7
10
3
4
5
6
7
8
0
0
I