Dip switch, Braking resistor – Metalfab SEW Eurodrive MOVIMOT MM..C User Manual
Page 89

Operating Instructions – MOVIMOT® MM03C - MM3XC
89
7
Additional information for mounting close to the motor
Startup of Standard Design
DIP switch
With mounting of the MOVIMOT
®
inverter close to the motor, set DIP switch S1/5 to ON
which is different than the factory setting.
Braking resistor
•
With motors without brakes, an internal braking resistor (BW1 or BW2) must be con-
nected to the MOVIMOT
®
.
•
With brake motors, no braking resistor may be connected to the MOVIMOT
®
.
Mounting of the
MOVIMOT
®
inverter in the
field distributor
Observe the instructions in the corresponding manuals when mounting the MOVIMOT
®
inverter close to the motor in the field distributor:
•
PROFIBUS Interfaces, Field Distributors
•
InterBus Interfaces, Field Distributors
•
DeviceNet/CANopen Interfaces, Field Distributors
•
AS-Interfaces, AS-i field distributors
S1
1
2
3
4
5
Motor
protec-
tion
6
Motor
rating class
7
PWM
frequency
8
No-load
damping
Message
RS-485 address
2
0
2
1
2
2
2
3
ON
1
1
1
1
Off
Motor one
size smaller
Variable
(16, 8, 4 kHz)
On
OFF
0
0
0
0
On
adapted
4 kHz
Off
06487AXX
13
14
15
BW1 / BW
2
MOVIMOT
®
0
0
I