Installation instructions
Electrical Installation with Integrated AS-Interface
Protection
devices
•
MOVIMOT
®
drives are equipped with integrated protective overload devices that are
making external overload devices obsolete.
UL compliant
installation
•
Use only copper cables with the temperature range 60 / 75 °C.
•
The permitted tightening torques for MOVIMOT
®
power terminals are:
– 1.5 Nm (13.3 lb.in).
•
MOVIMOT
®
are suited for operation on voltage supply systems with grounded star
(TN and TT systems) supplying a maximum supply current of 5000 A
AC
and having
a maximum rated voltage of 500 V
AC
(MM03C-503 to MM3XC-503). The perfor-
mance data of the fuses must not exceed 35 A/600 V.
•
Only use tested units with a limited output voltage (V
max
= 30 V
DC
) and limited output
current (I
≤
8 A) as an external 24 V
DC
voltage source.
•
UL certification applies only to operation in voltage supply systems with voltages to
ground up to 300 V.