Configuring a pico-link network, Changing the pico-link configuration – Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual
Page 95
Publication 1760-UM002B-EN-P - March 2005
Commissioning 3-17
Configuring a Pico-Link Network
The Pico-Link network can only be configured from station 1.
Requirement:
All stations are correctly connected to the network and the termination
resistors have been connected.
All stations have a power supply and are in STOP mode. The POW LED is
permanently lit. The NET LED is permanently lit.
1.
Proceed to the CONFIGURE menu item and press the OK button.
You will be asked to acknowledge whether you want to configure the
system.
2.
Press the OK button.
The message on the left appears:
All NET LEDs on the stations which are assigned station numbers
higher than 1 (2 to 8) switch to the OFF state of the Pico-Link.
As soon as the configuration has been successfully completed, the NET
LEDs on all stations flash. The Pico-Link network is ready for
operation.
If you want to overwrite the station address press the OK button. The
configuration can be aborted by pressing the ESC button.
Changing the Pico-Link Configuration
The configuration of the Pico-Link network can be modified at any time at
station 1, physical location 1.
IMPORTANT
If the connected stations are configured, all stations
automatically switch to the STOP mode.
NET PARAMETERS..
STATIONS...
CONFIGURE
CONFIGURE?
CONFIGURATION
IN
PROGRESS.
IMPORTANT
An error message will appear if a station is assigned a
station address which does not correspond to the
physical location in the station list.
ERR: ID-CONFLICT
OVERWRITE
CONFIGURATION ?