beautypg.com

Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 378

background image

Publication 1760-UM002B-EN-P - March 2005

A-6 Specifications

Electromagnetic compatibility (EMC)

Electrostatic discharge (ESD),
(IEC/EN 61000-4-2, severity level 3)

Air discharge: 8 kV
Contact discharge: 6 kV

Electromagnetic fields (RFI),
(IEC/EN 61000-4-3)

10 V/m

Radio interference suppression (EN 55011,
IEC 61000-6-1, 2, 3, 4), limit class

B

Burst (IEC/EN 61000-4-4, severity level 3)

Power cables: 2 kV
Signal cables: 2 kV

High energy pulses (Surge)
(IEC/EN 61000-4-5, severity level 2), power
cable symmetrical

0.5 kV

Line-conducted interference (IEC/EN
61000-4-6)

10V

Overvoltage category

11

Pollution degree

2

Dielectric strength

Measurement of the air clearance and
creepage distance

EN 50178, UL 508, CSA C22.2, No 142

Dielectric strength

EN 50178

Tools and cable cross-sections

Solid

0.2 mm

2

(24 AWG) minimum to

4 mm

2

(12 AWG) maximum

Flexible with ferrule

0.2 mm

2

(24 AWG) minimum to

2.5 mm

2

(12 AWG) maximum

Slot-head screwdriver, width

3.5 mm x 0.5 mm (0.14 in x 0.02 in)

Table A.6 General Ambient Conditions