Publication 1760-UM002B-EN-P - March 2005

2-34 Installation

Connection Cable

4-pair twisted cable; see General on page A-1

Figure 2.41 Connection assignment

ECAN_H data cable, pin 1, cable pair A

ECAN_L data cable, pin 2, cable pair A

Ground cable GND, pin 3, cable pair B

Select cable SEL_IN, pin 4, cable pair B

Material for Self-Manufactured Cables

• 100m cable: 1760-CBL-INT300
• Crimping tool for RJ45 plug

Bus Termination Resistor

The first and last stations in the network must be provided with a bus
termination resistor.

• Value: 124 Ω
• Termination connector: 1760-TERM1

A

1 ECAN_H

A

2 ECAN_L

B

3 GND (Ground)

B

4 SEL_IN

IMPORTANT

Minimum operation with Pico-Link functions with the
cables ECAN_H, ECAN_L and GND. The SEL_IN cable
is only used for automatic addressing.

Table 2.42 Prefabricated Cables (RJ45 plug on both ends)

Catalog Number

Cable Length (cm)

1760-CBL-INT01

30

1760-CBL-INT03

80

1760-CBL-INT05

150