beautypg.com

Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 161

background image

Publication 1760-UM002B-EN-P - March 2005

Wiring with Pico GFX-70 4-51

The comparison result of the function block BC01 is: BC01EQ = 0, the data
block ranges do not have the same content.

MB18 are MB68 not identical.

Example:
Comparison of marker blocks, definition of a marker range in a different
format.

Two marker blocks are to be compared. Block 1 starts at MB60, Block 2 at
MD80. Each block is 6 bytes long.

Parameters of BC01 function block:
Comparison range 1:

>I1 MB60

Comparison range 2:

>I2 MD80

Number of bytes:

>NO 6

Comparison range
1

Value of marker
range 1 (decimal)

Comparison range
2

Value of marker
range 2 (decimal)

MB15

45

MB65

45

MB16

62

MB66

62

MB17

102

MB67

102

MB18

65

MB68

57

IMPORTANT

The comparison is in byte format. MD80 has 4 bytes.
Therefore the first two bytes of MD81 are also compared.