beautypg.com

Value range – Rockwell Automation 1760-xxxx Pico GFX-70 Controllers User Manual User Manual

Page 179

background image

Publication 1760-UM002B-EN-P - March 2005

Wiring with Pico GFX-70 4-69

Figure 4.29 Pico GFX-70 circuit diagram with counter relay

Parameter Display and Parameter Set for the Counter Relay

In the parameter display of a counter relay you change set point values and/or
the preset value and the enabling of the parameter display.

Value Range

The function block operates in the integer range from
-2147483648 to 2147483647.

Behavior when value range is exceeded

The function block sets the switching contact C .. CY to the status 1 and
retains the value of the last valid operation.

I 05---------------------------[ C 20C_

I 06---------------------------[ C 20RE

I 07---------------------------[ C 20D_

I 08---------------------------[ C 20SE

C 20OF-------------------------[ Q 01

C 20FB-------------------------[ Q 02

C 20ZE-------------------------[ Q 03

C 20CY-------------------------S M 42

C 20

+

>SH

>SL

>SV

QV>

C 20

Counter relay function block number 20

+

Appears in the parameter display

>SH

Upper set point

>SL

Lower set point

>SV

Defined actual value (Preset)

QV>

Actual value in RUN mode

IMPORTANT

The counter C counts every rising edge on the counter
input. If the value range is exceeded, the switching contact
C ..CY switches to status 1 for one cycle per rising edge
detected.