beautypg.com

Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 97

background image

Publication 1404-UM001D-EN-E - October 2004

Communications 4-37

The Powermonitor 3000 supports the following network requests:

IMPORTANT

Please give particular attention to the messaging and
software version compatibility information in the
table. If you are replacing a Series A Ethernet
Powermonitor 3000 with a Series B unit, you may
need to upgrade software or modify the
communications programming of your controller
ladder programming or client application to
re-establish communications.

Table 4.10 Series A and Series B Comparison

Function

Series A (Comms FRN
2.01 or 2.02)

Series B

Communications protocol

CSP (PCCC) and/or
EtherNet/IP

EtherNet/IP only
Encapsulated PCCC
(Comms FRN 1.22 or later)

Protocol select

Yes

N/A

Bootp support

Yes

No

Data rate

10 Mbps

10/100 Mbps

Web page

Fixed web page

Configurable web page

Flash upgradeable

Uses special loader

Uses ControlFlash

LED indicators

Link, RX, TX

LNK, ACT, STATUS`

Network Demand Synch

No

Yes

SNTP capable

No

Yes

I/O Communications

No

Yes

CIP Generic messaging

Yes

Yes

PLC-5 Typed CIP messaging

Yes

Yes

CIP Data Table messaging

Yes

Yes, Comms FRN 1.21 or
later

SLC 500 Typed CIP messaging

Yes

Yes, Comms FRN 1.21 or
later

RSPower32 support

2.10 and later

2.40 and later

RSEnergyMetrix support

Yes

Yes

RSEnergy support

2.00.13 (CSP only)

No, upgrade to
RSEnergyMetrix