Ee table a.6), Table a.6 advanced device configuration, Advanced device configuration – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 183: Table a.6
Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-9
Table A.6 Advanced Device Configuration
CSP File No.
N12
Remote I/O BT
26
CIP Assy. Inst.
8 (Write), 9 (Read)
No. of Elements
25
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Units Default
Value
Comment
0
40201
Password
0 to 9999 -
0
Required to change configuration data.
Returns -1
1
40202
New password
0 to 9999 -
-1
-1 = no action; 0 to 9999 = new password;
returns -1
2
40203
Demand period length
-99 to
+99
Min
15
Refer to Demand Calculation on page 3-9
3
40204
Number of demand periods
1 to 15
-
1
4
40205
Predicted demand type
0 to 2
-
0
0 = instantaneous; 1 = 1st order; 2 = 2nd order
5
40206
KYZ control source
0 to 8
-
7
0 = None (forcing
only)
1 = Wh Forward
2 = Wh Reverse
3 = VARh Forward
4 = VARh Reverse
5 = Vah
6 = Ah
7 = Setpoints
8 = Discrete control (RIO,
DeviceNet)
6
40207
KYZ pulse output scale
1 to
30000
-
10
Refer to Relay and KYZ Output Operations on
page 6-1
7
40208
KYZ pulse output width
0, 40 to
2000
mSec
0
0 = KYZ-style transition
40 to 2000 = pulse duration
8
40209
Relay control source
0 to 8
-
7
Same choices as KYZ control source
9
40210
Relay pulse output scale
1 to
30000
-
10
Refer to Relay and KYZ Output Operations on
page 6-1
10
40211
Relay pulse output width
0, 40 to
2000
mSec
100
0 = KYZ-style transition
40 to 2000 = pulse duration
11
40212
RMS resolution
0 to 1
-
0 (M4)
1 (M5, 6 or 8)
0 = Nominal
1 = High
12
40213
RMS result averaging
0 to 1
-
0 (M4)
1 (M5, 6 or 8)
0 = No averaging.
1 = Average of the last 8 results
13
40214
Frequency averaging
0 to 1
-
1
0 = none; 1 = last 8 cycles
14
40215
Restore factory default
config
0 to 1
-
0
0 = No action 1 = Restore factory default settings
15
40216
Clear status input counters
0 to 3
-
0
0 = No action
1 = Clear counter #1
2 = Clear counter #2
3 = Clear both
16
40217
Wdog action
0 to 1
-
1
0 = Restart, log an event and halt operation
1 = Restart, log an event and resume
Refer to Watchdog Timeout Action on page 3-28.