Powermonitor 3000 Data Tables A-9

Table A.6 Advanced Device Configuration

CSP File No.

N12

Remote I/O BT

26

CIP Assy. Inst.

8 (Write), 9 (Read)

No. of Elements

25

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Units Default

Value

Comment

0

40201

Password

0 to 9999 -

0

Required to change configuration data.
Returns -1

1

40202

New password

0 to 9999 -

-1

-1 = no action; 0 to 9999 = new password;
returns -1

2

40203

Demand period length

-99 to
+99

Min

15

Refer to Demand Calculation on page 3-9

3

40204

Number of demand periods

1 to 15

-

1

4

40205

Predicted demand type

0 to 2

-

0

0 = instantaneous; 1 = 1st order; 2 = 2nd order

5

40206

KYZ control source

0 to 8

-

7

0 = None (forcing
only)
1 = Wh Forward
2 = Wh Reverse
3 = VARh Forward
4 = VARh Reverse

5 = Vah
6 = Ah
7 = Setpoints
8 = Discrete control (RIO,
DeviceNet)

6

40207

KYZ pulse output scale

1 to
30000

-

10

Refer to Relay and KYZ Output Operations on
page 6-1

7

40208

KYZ pulse output width

0, 40 to
2000

mSec

0

0 = KYZ-style transition
40 to 2000 = pulse duration

8

40209

Relay control source

0 to 8

-

7

Same choices as KYZ control source

9

40210

Relay pulse output scale

1 to
30000

-

10

Refer to Relay and KYZ Output Operations on
page 6-1

10

40211

Relay pulse output width

0, 40 to
2000

mSec

100

0 = KYZ-style transition
40 to 2000 = pulse duration

11

40212

RMS resolution

0 to 1

-

0 (M4)
1 (M5, 6 or 8)

0 = Nominal
1 = High

12

40213

RMS result averaging

0 to 1

-

0 (M4)
1 (M5, 6 or 8)

0 = No averaging.
1 = Average of the last 8 results

13

40214

Frequency averaging

0 to 1

-

1

0 = none; 1 = last 8 cycles

14

40215

Restore factory default
config

0 to 1

-

0

0 = No action 1 = Restore factory default settings

15

40216

Clear status input counters

0 to 3

-

0

0 = No action
1 = Clear counter #1

2 = Clear counter #2
3 = Clear both

16

40217

Wdog action

0 to 1

-

1

0 = Restart, log an event and halt operation
1 = Restart, log an event and resume
Refer to Watchdog Timeout Action on page 3-28.