beautypg.com

Instance attributes, Semantics, Instance attributes semantics – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 318

background image

Publication 1404-UM001D-EN-E - October 2004

F-12 Powermonitor 3000 EtherNet/IP Device Profile

Instance Attributes

Semantics

The NVS Object’s attributes are defined as follows:

Revision - The current major and minor revision of the NVS Object
itself.

Status - The status attribute reports the current status of the NVS
Object instance. The Status can be any one of the following:

Instance Revision - The current major and minor revision of
firmware or data represented by this instance of the NVS Object.

Table F.23

Attr ID

Acces
s

Name

Data Type

Default
Value

1

Get

Status

UINT

2

Get

Revision

UINT

1

Table F.24

Value

Description

0

Nothing new / No Update

1

Success on Transfer

2

Success on Programming

3

Failure on Transfer

4

Failure on Programming

5

Faulted

TIP

The DC's web content flash file does not utilize
revision levels. Consequently, instance 2 of the NVS
Object always reports a major / minor revision of 1.0.