Metering power factor results, Table a.13 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 195
Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-21
Table A.13 Metering Power Factor Results
CSP File No.
F19
Remote I/O BT
33
CIP Assy. Inst.
18
No. of Elements
13
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Units
Range
Comment
0
30501-02 L1 True Power Factor
Percent
-100 to 100
Ratio between power and apparent power.
+ = Lead
- = Lag
1
30503-04 L2 True Power Factor
-100 to 100
2
30505-06 L3 True Power Factor
-100 to 100
3
30507-08 3-phase True PF
-100 to 100
4
30509-10 L1 Displacement Power Factor
-100 to 100
Cosine of the phase angle between the fundamental
voltage and current.
+ = Lead
- = Lag
5
30511-12 L2 Displacement Power Factor
-100 to 100
6
30513-14 L3 Displacement Power Factor
-100 to 100
7
30515-16 3-phase Displacement PF
-100 to 100
8
30517-18 L1 Distortion Power Factor
0 to 100
The ratio between the magnitude of the fundamental
and the sum of the magnitudes for all of the current
harmonics.
9
30519-20 L2 Distortion Power Factor
0 to 100
10
30521-22 L3 Distortion Power Factor
0 to 100
11
30523-24 3-phase Distortion PF
0 to 100
12
30525-26 Metering iteration
-
0 to 32767
Increments by 1 to 32767, rolls over to 0