Table a.26 is, Table a.27 is th, Table a.27 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 211: Event log configuration/read-back record select, Table a.26, Event log results
Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-37
Table A.26 Event Log Configuration/Read-Back Record Select
CSP File No.
N28
Remote I/O BT
9
CIP Assy. Inst.
32 (Write), 33 (Read)
No. of Elements
6
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Applies to:
Table 27: Event log results
Table 49: Event log text
Element
No.
Modbus
Address
Element name
Range
Default
Value
Comment
0
41001
Password
0 to 9999
0
Required for configuration, -1 for readback
select, returns -1.
1
41002
DeviceNet unique write identifier
-32768 to 32767
0
Refer to DeviceNet Unique Write Identifier on
page 4-36
2
41003
Read-back mode
0 to 6
2
Refer to Configuring the Event Log Using
Communications on page 7-4
3
41004
Enable/disable logging status
input changes
0 to 1
0
4
41005
# events in the event log
1 to 50 (M4,M5)
1 to 100 (M6, M8)
-
5
41006
Enable/disable logging of
time/date set
0 to 1
1
Table A.27 Event Log Results
CSP File No.
N29
Remote I/O BT
21
CIP Assy. Inst.
34
No. of Elements
14, 17 or 18 (see table)
User Configurable No
Data Type
Integer
Data Access
Read only
PM3000 Type
See table
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name
Range
Comment
0
30901
•
• • Reserved
0
Returns 0.
1
30902
•
• • Internal identifier
0 to 32768
Refer to Reading Data from the Event Log
Using Communications on page 7-5