C-18 Sample Applications

Refer to Devicenet Scanner Module Installation Instructions,
publication 1747-5.8, for a detailed description of all coding.

Word M0:1.224

A unique TXID (Transmit Identifier) and Command byte is needed for
this word. The valid command codes are:

• 1 = Execute transaction block
• 4 = Delete transaction from response queue

A command byte of 1 is used first to start the explicit message. After a
response has been received from the scanner, a command byte of 4 is
used to remove this transaction from the scanner. If the command
byte of 4 is not written to the SLC-500 DeviceNet Scanner, then it does
not process further transactions.

Table C.1

TXID

cmd/status

Port

Size

Service

MAC ID

Class

Instance

Attributes

Table 3.B

TXID

Cmd

TXID x 256 + Cmd

20 x 256 + 1

5121