Ansi/ieee tested, Technical specifications, Measurement accuracy and range – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 301
Publication 1404-UM001D-EN-E - October 2004
Technical Specifications D-3
The Bulletin 1404 Display Module is rated as IP65 degree of
protection per International Standard IEC 529. It is rated as Type 4
(Indoor) per NEMA and UL 508.
Follow the recommended installation guidelines to maintain these
ratings.
ANSI/IEEE Tested
Meets or exceeds the Surge Withstand Capability (SWC) C37.90.1 -
1989 for protective relays and relay systems on all power connection
circuit terminations.
Technical Specifications
Measurement Accuracy and Range
See table below for the rating of each parameter
Table D.1 Measurement Accuracy and Range
Parameter
Accuracy in % of Full Scale at +25°C 50/60 Hz Unity Power Facator
Nominal/Range
M4
M5
M6
M8
Voltage Sense Inputs: V1, V2,
V3
±0.2%
±0.05%
±0.05%
±0.05%
347V/15 to 399V
L-N
RMS
600V/26 to 691V
L-L
RMS
Current Sense Input: I1, I2, I3,
I4
±0.2%
±0.05%
±0.05%
±0.05%
5A/50 mA – 10.6A
RMS
Frequency
±0.05 Hz
±0.05 Hz
±0.05 Hz
±0.05 Hz
50 or 60 Hz/40 to 75 Hz
Power Functions: kW, kVA,
kVAR
Demand Functions: kW, kVA
Energy Functions: kWH, kVAH
ANSI C12.16 and
EN 61036 Class 1
Accuracy
ANSI C12.20 and
EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)
ANSI C12.20 and
EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)
ANSI C12.20 and
EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)
Metering Update Rates
55 to 80 ms
45 to 70 ms
45 to 75 ms
40to 90 ms