Table a.7 native communication configuration, Native communication configuration, Table a.7 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 184
Publication 1404-UM001D-EN-E - October 2004
A-10 Powermonitor 3000 Data Tables
17
40218
Force relay output
0 to 3
-
0
0 = No change
1 = Force energize the relay
2 = Force de-energize the relay
3 = Release force of relay output
Overrides setpoint or pulse output control
18
40219
Force solid-state KYZ output 0 to 3
-
0
19
40220
Default relay state in event
of communications loss
0 to 3
-
0
0 = Last state / resume
1 = Last state / freeze
2 = De-energize / resume
3 = De-energize / freeze
Refer to Communications Loss Behavior on
page 6-4
20
40221
Default KYZ state in event
of communications loss
21
40222
DM text scroll rate
0 to 1
-
1
0 = Slow; 1 = Fast
22
40223
Energy counter rollover
4 to 15
Digits 15
Refer to Configurable Energy Counter Rollover
on page 3-9
23
40224
Forced demand sync delay
0 to 900
Seco
nds
10
0 = Disable, 1 to 900 = number of seconds delay
24
40225
Reserved
0
-
0
Reserved. Must be 0 on a write, returns 0.
25
40226
Reserved
0
-
0
Reserved. Must be 0 on a write, returns 0.
Element
No.
Modbus
Address
Element name
Range
Units Default
Value
Comment
Table A.7 Native Communication Configuration
CSP File No.
N13
Remote I/O BT
11
CIP Assy. Inst.
10 (Write), 11 (Read)
No. of Elements
6
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Units Default
Value
Comment
0
40301
Password
0 to 9999 -
0
Valid password required to change configuration data.
Returns -1
1
40302
Protocol
0
-
0
0 = DF1 half-duplex slave
1 = Modbus RTU slave
2 = Auto Sense - Selects the protocol based on the incoming
communication packets
2
40303
Delay
0 to 15
5 mS
2
(10mS)
Specifies the delay before responding to an external request,
useful with slow external devices (such as RF modems).
3
40304
Baud rate
0 to 4
-
3
0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud