Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 112

background image

Publication 1404-UM001D-EN-E - October 2004

4-52 Communications

This message transfers 9 floats from table F8:0 to the Powermonitor
3000 table F10. The Powermonitor 3000 address is at node 4, local
message.

How to Clear or Preset Energy Counters Using Communications

You may clear or preset the energy counters by performing a table
write to Table A.14 Metering Real and Apparent Energy Results or
Table A.15 Metering Reactive Energy and Amp-Hour Results. These
read/write tables each contain 22 integer elements as follows:

Password: required to clear or preset an energy counter, returns

-1

Parameter select: bitfield used to select parameter for clearing or

presetting. See below

Energy counter values: expressed in integer-array format, see

page 4-18

Metering iteration: increments by 1 with each new set of results,

rolls to 0 at 32,767

The Parameter select bitfield value selects the parameter or parameters
to be cleared or preset during the current write, as shown in the table
below.