beautypg.com

Configuring setpoints using the display module, Viewing setpoint data using the display module – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 125

background image

Publication 1404-UM001D-EN-E - October 2004

Setpoint Programming and Operation 5-11

Example 3 – Oscillogram capture on demand: To use setpoint 3 to
capture an oscillogram when you push a button connected to status
input number 2, you could use these settings.

Configuring Setpoints Using the Display Module

You may configure setpoint operations by navigating through the
PROG

> PASS? > CONFIGURATION > SETPOINT menus, selecting a

setpoint number and programming the appropriate parameters.

Viewing Setpoint Data Using the Display Module

You may view setpoint setup parameters and status by navigating
through these menus: DISP > CONFIGURATION > SETPOINT,
selecting the setpoint number and scrolling through the setpoint setup
parameters, status and accumulated activated time.

Writing Setpoint Configuration Using Communications

To configure setpoint operations using communications, the client
performs a table write to Table A.18 Setpoint Setup/Read-Back Select
and Status
. This read/write data table of 16 integer elements includes
the following:

Setpoint number

3

Setpoint type

32 - Status input No. 2

Setpoint evaluation condition

4 - Equal

Setpoint high limit

1 - On

Setpoint low limit

Not used

Setpoint action delay

N/A (M4, M5)
5 tenths of a second (M6, M8)

Setpoint release delay

N/A (M4, M5)
5 tenths of a second (M6, M8)

Setpoint action type

43 - Capture oscillogram