Discrete data, Table a.3 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 180
Publication 1404-UM001D-EN-E - October 2004
A-6 Powermonitor 3000 Data Tables
Table A.3 Discrete Data
CSP File No.
N9
Remote I/O BT
10
CIP Assy. Inst.
3
No. of Elements
6
User Configurable No
Data Type
Integer
Data Access
Read Only
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Comment
0
30001
Relay output status
0 to 3
0 = De-energized & not forced
1 = Energized & not forced
2 = Force De-energized
3 = Force Energized
1
30002
Solid-state KYZ output
status
2
30003
Alarm output word
0 to FFFF Bitfield indicating state of the 16 alarm output flags; 0 = released, 1 = asserted.
Bit 0 = relay/setpoint output flag 1
Bit 1 = KYZ/setpoint output flag 2
Bit 2 = setpoint output flag 3
…
Bit 15 = setpoint output flag 16
3
30004
Status inputs state
0 to 3
Bit 0 = status input #1; 0 = open, 1 = contact closure detected
Bit 1 = status input #2; 0 = open, 1 = contact closure detected
Bit 2 = demand sync timeout; 1 = the demand delay expired before the next
expected external demand sync. This bit clears when the next external demand
sync occurs. Refer to Table A.6 Advanced Device Configuration element 23.
Bits 3-15 = unused (always 0)
4
30005
Status input #1 counter
0 to
29999
Counts to 29,999,rolls over to 0
5
30006
Status input #2 counter