beautypg.com

Event log configuration options, Viewing the event log using the display module – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 134

background image

Publication 1404-UM001D-EN-E - October 2004

7-2 Data Logging

Event Log Configuration Options

There are two options in the Event Log setup.

• You may choose to log or ignore (ignore is default) status input

change-of-state. You may make this configuration setting using
the Display Module by navigating through these menus: PROG >
PASS

? > CONFIGURATION > EVENT LOG and setting the Log

Status Inputs parameter from No to Yes. You may also make this
selection using communications.

• You may choose to log or ignore (log is default) changes to the

date and time setting. You may make this selection only using
communications.

These choices provide you with the flexibility to ignore routine
occurrences, thereby increasing the time that important events are
stored. For example, a status input may count pulses from a water or
gas meter. Or, the unit may be connected to an energy logging system
such as RSEnergyMetrix that synchronizes the time every night at
midnight. In either case, important events would likely be overwritten
by routine, nuisance events.

Viewing the Event Log Using the Display Module

You may view the entries in the Event Log by navigating through
DISP

. > LOGS > EVENT LOG. The event number shows up in the top

line, and in the bottom line an event description followed by the
event time stamp scrolls across the display. Table 7.1 lists the event
codes as shown on the Display Module.

Table 7.1 Event Codes

Event Type Name

Event Type
Shown by DM

Event Type
Number

Event Command Code

No Event

No Evnt

0

0

Setpoint Activated

Set##A

(1)

1

Setpoint Number (1-10)

Setpoint Deactivated

Set##D

(1)

2

Setpoint Number (1-10)

Relay Forced Energized

Rly# F1

(1)

3

Relay Number (1-2)

Relay Forced De-energized

Rly# F0

(1)

4

Relay Number (1-2)

Relay No Force Option

Rly# NF

(1)

5

Relay Number (1-2)

Status Input Set

S# On

(1)

6

Status Input Number(1-2)