Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 155

background image

Publication 1404-UM001D-EN-E - October 2004

Advanced Features 8-5

The total number of data points is 4600 for capture type 0, 1 and 2
and 9200 for capture types 3, 4 and 5.

Each data point is expressed in calibrated analog-to-digital (A/D)
converter counts with a resolution of 8192 (13-bit w/sign) or 128 (7-bit
w/sign). A client may calculate the primary-side instantaneous voltage
or current magnitude of each data point using the following formula:

Where:

• M

i

= instantaneous value of the voltage or current data point

• M

(max rms)

= max rms magnitude

= 399.0 line-to-neutral volts for channels 1, 3 and 5
= 691.1 line-to-line volts for channels 1, 3 and 5
= 10.6 amperes for channels 2, 4, 6 and 7

• R

max

= maximum resolution

= 8192 for 13-bit w/sign, capture types 0, 1 and 2
= 128 for 7-bit w/sign, capture types 3, 4 and 5

• N

t

= PT or CT ratio

= PT or CT primary / PT or CT secondary

• M

data

= value of the data point from Table 39

For example, consider the following capture:

• PT primary = 13.8 kV
• PT secondary = 120 V
• CT primary = 100 A
• CT secondary = 5 A
• Delta voltage mode (line-to-line)
• Capture type = 2

You would multiply each data point by the following factor to
correctly display the waveform:

N

datapoint_oscillogram

N

block

1

(

) N

datapoint_this_read

+

=

N

datapoint_oscillogram

= the sequence number of the data point in the oscillogram channel

N

block

= the block number

N

datapoint_this_read

= the data point number (1 to 20 or 1 to 50) in the current read

M

i

M

max rms

(

)

2

R

max

--------------------------------------

N

t

M

data

=