Network demand sync and time configuration, Table a.52 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 238

background image

Publication 1404-UM001D-EN-E - October 2004

A-64 Powermonitor 3000 Data Tables

Table A.52 Network Demand Sync and Time Configuration

CSP File No.

N52

Remote I/O BT

-

CIP Assy. Inst.

65, 66

No. of Elements

20

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

Ethernet Series B

Element
No.

Modbus
Address

Parameter name

Range

Default
Value

Description

0

41901

Password

0 to
9999

0

On a write, the correct password is required to change
configuration data. On a read, -1 is returned.

1

41902

Input mode

0 to 3

3

Refer to Network Demand / Time Configuration on
page 3-29
.

2

41903

Broadcast port number

300 to
400

300

3

41904

Time server IP address-byte
1

0 to 255 0

4

41905

Time server IP address-byte
2

5

41906

Time server IP address-byte
3

6

41907

Time server IP address-byte
4

7

41908

Time zone

-12 to 12 0

8

41909

Time set update interval

0 to
32766

60 (Sec)

9

41910

SNTP IP address 2, octet 1

0 to 255

0

SNTP IP address 2 is a back-up server address when
the first address fails.

10

41911

SNTP IP address 2, octet 2

0

11

41912

SNTP IP address 2, octet 3

0

12

41913

SNTP IP address 2, octet 4

0

13

41914

SNTP IP address 3, octet 1

0

SNTP IP address 3 is a back-up server address when
the secnond address fails.

14

41915

SNTP IP address 3, octet 2

0

15

41916

SNTP IP address 3, octet 3

0

16

41917

SNTP IP address 3, octet 4

0

17

41918

Reserved

0

0

Reserved for future use.

On a write, only a 0 is accepted. On a read, always
returns 0.

18

41919

Reserved

0

0

19

41920

Reserved

0

0