beautypg.com

Class specific services – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 338

background image

Publication 1404-UM001D-EN-E - October 2004

G-14 Powermonitor 3000 ControlNet Device Profile

Class Specific Services

Update Service

The Update service is sent by a remote application to signal the
beginning of an update session. The service accepts the following
request parameters:

The DC will respond to the Update service with the following
response parameters:

Transfer Service Parameters

The Transfer service is sent repeatedly by a remote application to
transfer the actual update data to the DC a chunk at a time. The
service accepts the following parameters:

Table G.23 NNVS Ojbect Class Specific Services

Service
Code

Class/Instance
Usage

Service Name

0x4B

Instance Update

0x4D

Instance

Transfer

Table G.24 Request Parameters

Parameter

Data Type Description

Size

UDINT

Number of bytes in this update

Base Address

UDINT

Starting address for the storage of this update

Table G.25 Response Parameters

Parameter

Data Type Description

Boot Update
Flag

UINT

Indicates if the Boot Code is to be updated.

Incremental
Burn

UINT

Number of chunks transferred prior to being programmed.

Transfer Size

UINT

Chunk size for the transfers. (128 bytes)

Instance
Revision

UINT

Major and minor revision of the firmware or data
represented by this instance

Upload Size

UDINT

Size of the upload in bytes.