Reading the Load Factor Log

To select the read-back mode or record, an auto reset/store day of the
month, or issuing a manual reset/store command, perform a table
write to Table A.41. Load factor log data is not available via Modbus
communications. This read/write table contains 6 integer elements as
follow:

Password: required for changing the auto clear/reset day or

manual clear/reset command. Use -1 if only selecting read-back
mode or record. Range 0000 to 9999, default 0000. Returns -1

Record select: selects the next read-back record
Read-back mode: 0 = auto-increment record number after each

read, 1 = manual increment. Auto-increment not supported in
DeviceNet and Ethernet optional communications.

Manual clear/reset command: 0 = do nothing, 1 = manual

clear/reset command (see above)

Auto clear/reset day: Selects the day of month for automatically

storing and clearing the current in-process record. Range 0 to 31;
0 disables automatic clear/reset, 1 to 28 selects day of month, 29
to 31 selects last day of month

Reserved: reserved element must be 0 on a write, returns 0

The results table is Table A.42. You may read the in-process Record 0
or one of the 12 logged records. This table contains the following 14
floating-point elements:

Peak demand power: expressed in watts. Range 0.0 to 999.9*10

21

Average demand power: expressed in watts. Range 0.0 to

999.9*10

21

Load factor power: expressed in per cent. Range 0.0 to 100.0
Peak demand reactive power: expressed in VARs. Range 0.0 to

999.9*10

21

Average demand reactive power: expressed in VARs. Range 0.0

to 999.9*10

21

Load factor reactive power: expressed in per cent. Range 0.0 to

100.0

Peak demand apparent power: expressed in VARs. Range 0.0 to

999.9*10

21

Average demand apparent power: expressed in VARs. Range 0.0

to 999.9*10

21

Load factor apparent power: expressed in per cent. Range 0.0 to

100.0