Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 24
Publication 1404-UM001D-EN-E - October 2004
2-12 Product Description
Table 2.7 Ethernet Optional Communications (Series A catalog numbers ending in
-ENT)
LED
LED Color
LED State and Communications
Condition
Link
Off
Ethernet connection is inactive
Steady Green
Ethernet connection is active
RX
Off
Ethernet is idle, no active data present on
port
Flashing Red
Active data is present on Ethernet port
TX
Off
Powermonitor 3000 is not transmitting any
data through the Ethernet port
Flashing Red
Powermonitor 3000 is transmitting data
Table 2.8 EtherNet/IP Optional Communications (Series B catalog numbers ending
in -ENT)
LED
LED Color
LED State and Communications
Condition
LNK
Off
No valid physical Ethernet connection
Steady Green
Valid physical Ethernet connection
ACT
Strobing or
Solid Yellow
Powermonitor 3000 transmitting onto
Ethernet
F1
Off
Not Used
F2
Off
Not Used
NETWORK STATUS
Off
No power
Flashing Green
No established connections
Steady Green
Connected; has at least one established
connection
Flashing Red
Connection timeout; one or more
connections to this device has timed-out
Steady Red
Duplicate IP; the IP address assigned to this
device is already in use
Flashing Green/Red
Selftest; this device is performing a
power-up self test
Powermonitor 3000
wermonitor 3000
LINK
RX
TX
F1
LNK
ACT
F2
NETWORK
STATUS
Powermonitor 3000