A-12 Powermonitor 3000 Data Tables

Table A.8 Optional Communication Configuration

CSP File No.

N14

Remote I/O BT

24

CIP Assy. Inst.

12 (Write), 13 (Read)

No. of Elements

20

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

TIP

Select the table that applies to your Powermontior
3000.

Ethernet

Element
No.

Modbus
Address

Element name

Range

Units

Default

Value

Comment

0

40401

Password

0 to 9999

-

0

Valid password required to change
configuration data. Returns -1

1

40402

IP address byte a

0 to 255

-

128

Format: aaa.bbb.ccc.ddd. Static IP address
of this device (for example 130.151.32.86).
Address 0.0.0.0 enables bootp server to
assign IP address, subnet mask and
gateway. If connected to a network, IP
address must be unique. (255.255.255.255
is not permitted.)

2

40403

IP address byte b

1

3

40404

IP address byte c

1

4

40405

IP address byte d

Device ID Factory-assigned device ID

5

40406

Subnet mask byte a

0 to 255

-

255

Format aaa.bbb.ccc.ddd. Ignored if bootp
enabled.

6

40407

Subnet mask byte b

255

7

40408

Subnet mask byte c

255

8

40409

Subnet mask byte d

0

9

40410

Gateway IP address byte a

0 to 255

-

128

IP address of the gateway on this subnet
used to route

messages to other subnets (wide area
networking). Ignored if bootp enabled.

10

40411

Gateway IP address byte b

1

11

40412

Gateway IP address byte c

1

12

40413

Gateway IP address byte d

1

13

40414

Keep Alive Time (ENT Series A)
Reserved (ENT Series B)

0 to 3600

Seconds

30

The maximum time a socket is dedicated to
a connection that is not responding.
Reserved on Series B. Must be 0 on a
write, returns 0