A-12 Powermonitor 3000 Data Tables
Table A.8 Optional Communication Configuration
CSP File No.
N14
Remote I/O BT
24
CIP Assy. Inst.
12 (Write), 13 (Read)
No. of Elements
20
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
TIP
Select the table that applies to your Powermontior
3000.
Ethernet
Element
No.
Modbus
Address
Element name
Range
Units
Default
Value
Comment
0
40401
Password
0 to 9999
-
0
Valid password required to change
configuration data. Returns -1
1
40402
IP address byte a
0 to 255
-
128
Format: aaa.bbb.ccc.ddd. Static IP address
of this device (for example 130.151.32.86).
Address 0.0.0.0 enables bootp server to
assign IP address, subnet mask and
gateway. If connected to a network, IP
address must be unique. (255.255.255.255
is not permitted.)
2
40403
IP address byte b
1
3
40404
IP address byte c
1
4
40405
IP address byte d
Device ID Factory-assigned device ID
5
40406
Subnet mask byte a
0 to 255
-
255
Format aaa.bbb.ccc.ddd. Ignored if bootp
enabled.
6
40407
Subnet mask byte b
255
7
40408
Subnet mask byte c
255
8
40409
Subnet mask byte d
0
9
40410
Gateway IP address byte a
0 to 255
-
128
IP address of the gateway on this subnet
used to route
messages to other subnets (wide area
networking). Ignored if bootp enabled.
10
40411
Gateway IP address byte b
1
11
40412
Gateway IP address byte c
1
12
40413
Gateway IP address byte d
1
13
40414
Keep Alive Time (ENT Series A)
Reserved (ENT Series B)
0 to 3600
Seconds
30
The maximum time a socket is dedicated to
a connection that is not responding.
Reserved on Series B. Must be 0 on a
write, returns 0