Publication 1404-UM001D-EN-E - October 2004

Powermonitor 3000 Operations 3-11

First Order Projection

The first order demand projection utilizes the instantaneous demand
as a starting point, computes the trend of the instantaneous demand,
computes the time remaining in the interval, and performs a first order
projection of what the final demand will be at the end of the interval.
This method may be useful where your system has a significant base
load with additional loads that are switched in and out during the
interval.

Second Order Projection

The second order demand projection begins with the first order
projection. It computes the rate of change of the first order trend,
computes the time remaining in the interval, and performs a second
order projection of what the final demand will be at the end of the
interval. This method may be useful where your power system has
little or no base load and a load profile that increases over the
duration of the interval. A second order projection is more sensitive to
rapid load changes than the other methods.

Demand

1

t2

t1

----------------

P t

( ) t

d

t1

t2

=

(t2 - t1) = Elapsed interval duration and is less than T

Table 3.5 Energy and Demand Results

Parameter Description

Range

Units

Kilo-Watt Hours Forward

The total real power consumed

0 to 1.0x10

12

kWh

Kilo-Watt Hours Reverse

The total real power produced

Kilo-Watt Hours Net

The sum of forward and reverse power

Kilo-VAR Hours Forward

The total reactive power consumed

0 to 1.0x10

12

kVARh

Kilo-VAR Hours Reverse

The total reactive power produced

Kilo-VAR Hours Net

The sum of forward and reverse reactive power

Kilo-VA Hours Net

The total apparent power consumed

0 to 1.0x10

12

kVAh

Amp Hours Net

Accumulated amp-hours consumed.

0 to 1.0x10

12

Ah

Demand Current

The calculated demand for average current.

0 to 999.9x10

21

Amps

Max Demand Current

The maximum (peak) demand for current.

(included in Min/Max Log)

Demand Kilo-Watts

The calculated demand for real power.

0 to 999.9x10

21

kW

Max Demand Kilo-Watts

The maximum (peak) demand for real power
(included in Min/Max Log)