Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual
Page 190
Publication 1404-UM001D-EN-E - October 2004
A-16 Powermonitor 3000 Data Tables
RS-232
Element
No.
Modbus
Address
Element name
Range
Default
Value
Comment
0
40401
Password
0 to 9999
0
Required to change configuration data. Returns -1
1
40402
Hardware port
0 to 1
0
Select active port
0 = RS-232 port
1 = Native RS-485 port
2
40403
Protocol
0
0
0 = DF1 half-duplex slave
3
40404
Delay
0 to 15
2 (10mS)
Specifies the delay before responding to an external request.,
useful with slow external devices (such as RF modems)
4
40405
Baud rate
0 to 4
3
0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud
5
40406
RS-232 address
1 to 254
(1)
Identifies the device on the link. 0 is typically used by the DF1
master. 255 is the broadcast address
6
40407
Data format
0 to 2
0
Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Even parity, 8 data bits, 1 stop bit
2 = Odd parity, 8 data bits, 1 stop bit
7
40408
Flow Control
(Handshaking)
0 to 1
0
Data flow control for RS-232/RS-485 port.
0 = None
1 = Hardware RTS/CTS
8
40409
RTS On Delay
0 to 9995
ms
0
9
40410
10
40411
Specifies the minimum delay between characters that indicates
the end of a message packet. 0 = 3.5 character times.
11
40412
Reserved
0
0
Reserved. Must be 0 on a write, returns 0
12
40413
13
40414
14
40415
15
40416
16
40417
17
40418
18
40419
19
40420
(1) The default address is the same as the ‘Device ID’, which is assigned at the factory and can be found printed on the white label on the side of the master module. The device ID is
incremented for each device.