Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 212

background image

Publication 1404-UM001D-EN-E - October 2004

A-38 Powermonitor 3000 Data Tables

2

30903

• • Timestamp of event;

Year

Month/day

Hour/minute

Second/hsec

1998 to 2097

Refer to Expressing Data in Data Tables on
page 4-18.

3

30904

• •

0101 to 1231

4

30905

• •

0000 to 2359

5

30906

• •

0000 to 5999

6

30907

• • Event type

0 to 19

Refer to Table A.29 List of Event Types

7

30908

• • Event code

-

Refer to Reading Data from the Event Log
Using Communications on page 7-5

8

30909

• • Setpoint type

0 to 52

9

30910

• • Setpoint evaluation condition

0 to 5

10

30911

• • Setpoint level

integer

exponent

0 to 9999

11

30912

• •

-21 to 21

12

30913

• • Setpoint action/release delay

0 to 3600 (M4, M5)
0 to 30000 (M6, M8)

13

30914

• • Setpoint action

0 to 32 (M4, M5)
0 to 43 (M6, M8)

14

30915

• • Sustain limit timer

integer

exponent

0 to 9999

15

30916

• •

-4 to 21

16

30917

• • Capture identifier

0 to 999

17

30918

• Event Text Available

0 to 1

Refer to Event Log User Comment Field
(M8 only) on page 7-6

Element
No.

Modbus
Address

M4
M5

M
6

M
8

Element name

Range

Comment

Table A.28 Status Error Codes

Bits Hex

Description

bit 0

0001h

Master Module code flash status

bit 1

0002h

Master Module data flash status

bit 2

0004h

Master Module RAM Status

bit 3

0008h

Reserved for factory use

bit 4

0010h

Master Module NVRAM status

bit 5

0020h

Master Module data acquisition status

bit 6

0040h

Master Module real time clock status

bit 7

0080h

Reserved for factory use

bit 8

0100h

Reserved for factory use

bit 9

0200h

Display Module status

bit 10

0400h

Master Module watchdog timer status

bit 11

0800h

Master Module optional communications status

bit 12-15

1000h -8000h

Reserved for factory use