A-38 Powermonitor 3000 Data Tables
2
30903
•
• • Timestamp of event;
Year
Month/day
Hour/minute
Second/hsec
1998 to 2097
Refer to Expressing Data in Data Tables on
page 4-18.
3
30904
•
• •
0101 to 1231
4
30905
•
• •
0000 to 2359
5
30906
•
• •
0000 to 5999
6
30907
•
• • Event type
0 to 19
Refer to Table A.29 List of Event Types
7
30908
•
• • Event code
-
Refer to Reading Data from the Event Log
Using Communications on page 7-5
8
30909
•
• • Setpoint type
0 to 52
9
30910
•
• • Setpoint evaluation condition
0 to 5
10
30911
•
• • Setpoint level
integer
exponent
0 to 9999
11
30912
•
• •
-21 to 21
12
30913
•
• • Setpoint action/release delay
0 to 3600 (M4, M5)
0 to 30000 (M6, M8)
13
30914
•
• • Setpoint action
0 to 32 (M4, M5)
0 to 43 (M6, M8)
14
30915
• • Sustain limit timer
integer
exponent
0 to 9999
15
30916
• •
-4 to 21
16
30917
• • Capture identifier
0 to 999
17
30918
• Event Text Available
0 to 1
Refer to Event Log User Comment Field
(M8 only) on page 7-6
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name
Range
Comment
Table A.28 Status Error Codes
Bits Hex
Description
bit 0
0001h
Master Module code flash status
bit 1
0002h
Master Module data flash status
bit 2
0004h
Master Module RAM Status
bit 3
0008h
Reserved for factory use
bit 4
0010h
Master Module NVRAM status
bit 5
0020h
Master Module data acquisition status
bit 6
0040h
Master Module real time clock status
bit 7
0080h
Reserved for factory use
bit 8
0100h
Reserved for factory use
bit 9
0200h
Display Module status
bit 10
0400h
Master Module watchdog timer status
bit 11
0800h
Master Module optional communications status
bit 12-15
1000h -8000h
Reserved for factory use