beautypg.com

Table a.46, Table a.46 co, Transient capture results – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 231

background image

Publication 1404-UM001D-EN-E - October 2004

Powermonitor 3000 Data Tables A-57

Table A.46 Transient Capture Results

CSP File No.

N46

Remote I/O BT

60

CIP Assy. Inst.

57

No. of Elements

29 (DeviceNet only); 59 (All other communications types)

User Configurable No

Data Type

Integer

Data Access

Read only

PM3000 Type

M8 only

Element
No.

Modbus
Address

Element name

Range

Comment

0

-

Timestamp;

Month/day

Hour/minute

Second/hsec

0000 to 1231

Capture trigger timestamp, see page 4-18.

1

-

0000 to 2359

2

-

0000 to 5999

3

-

Capture #

1 to 6

Refer to Reading Transient Capture Data on page 8-21.

4

-

Channel number

1 to 7

5

-

Block number

See page 8-22

6

-

Reserved

0

7

-

Unique Transient Capture ID

0 to 30000

8

-

Reserved

0

9

-

Data Point 1

-8192 to 8191

10

-

Data Point 2

11

-

Data Point 3

12

-

Data Point 4

13

-

Data Point 5

14

-

Data Point 6

15

-

Data Point 7

16

-

Data Point 8

17

-

Data Point 9

18

-

Data Point 10

19

-

Data Point 11

20

-

Data Point 12

21

-

Data Point 13

22

-

Data Point 14

23

-

Data Point 15

24

-

Data Point 16

25

-

Data Point 17

26

-

Data Point 18

27

-

Data Point 19

28

-

Data Point 20