Page 226

background image

Publication 1404-UM001D-EN-E - October 2004

A-52 Powermonitor 3000 Data Tables

Table A.41 Load Factor Log Configuration/Read-Back Select

CSP File No.

N41

Remote I/O BT

16

CIP Assy. Inst.

49 (Write), 50 (Read)

No. of Elements

6

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

M6, M8 only

Applies to:

Table A.42 Load Factor Log Results

Element
No.

Modbus
Address

Element name

Range

Default
Value

Comment

0

-

Password

0 to 9999

0

Required for configuration or command,
-1 for readback select, returns -1.

1

-

Record to read-back

0 to 12

0

Refer to Reading the Load Factor Log on
page 8-17

2

-

Read-back mode

0 to 1

1

3

-

Clear peak / reset average command

0 to 1

0

4

-

Auto clear/reset day

0 to 31

31

5

-

Reserved

0

0