beautypg.com

Writing information through the scnr scanner – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, PRIOR to Firmware rev. 3.0 User Manual

Page 290

background image

Publication 1404-UM001D-EN-E - October 2004

C-36 Sample Applications

Writing Information through the SCNR Scanner

Observe the sample of the CIP_SETUP file for the writing the
configuration of the basic configuration table Instance 4 of the power
monitor.

When a 1 is written to location N9:11 the contents of file F13
WR_TRANSFR are sent to the power monitor. In this case starting
with float F13:0 through F13:8.

The writing of an integer file sends the contents of N14
WR_TRANSFR.

For further reading on the functionality of the 1747-SCNR scanner
refer to user manual Publication 1747-RM623B-EN-P.

TIP

The write procedure differs slightly from the read
process. N9:4 service has been changed to 0x10 or
16 decimal (Set Single Attribute). N9:6 is the write
instance assembly number of the power monitor
basic configuration table. N9:9 is the size of the
table in words for a 1404-M805A-CNT A. The size
for float tables is 2 times the number of elements.
Integer tables are 1 times the size of the table
elements.