A-26 Powermonitor 3000 Data Tables
Table A.18 Setpoint Setup/Read-Back Select and Status
CSP File No.
N23
Remote I/O BT
22
CIP Assy. Inst.
24 (Write), 25 (Read)
No. of Elements
16
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Units
Default
Value
Comment
0
40701
Password
0 to 9999
-
0
Required for configuration, -1 for readback
select, returns -1.
1
40702
Setpoint number
1 to 10 (M4, M5)
1 to 20 (M6, M8)
-
-
Refer to Writing Setpoint Configuration Using
Communications on page 5-11.
2
40703
Read-back mode
0 to 1
-
0
3
40704
Setpoint type
0 to 52
-
0
(1)
4
40705
Evaluation condition 0 to 5
-
0
5
40706
High limit
Integer
0 to 9999
Depends
on
setpoint
type
0
(1)
6
40707
High limit Exponent
-4 to 21
0
(1)
7
40708
Low limit
Integer
0 to 9999
0
(1)
8
40709
Low Limit Exponent
-4 to 21
0
(1)
9
40710
Action delay
0-3600 (M4, M5)
0-30000 (M6, M8)
Seconds
(M4, M5)
.1 Sec
(M6, M8)
0
10
40711
Release delay
0-3600 (M4, M5)
0-30000 (M6, M8)
Seconds
(M4, M5)
.1 Sec
(M6, M8)
0
11
40712
Output action
0 to 32 (M4, M5)
0 to 43 (M6, M8)
-
0
(1)
12
40713
Status
0 to 1
-
0
13
40714
Accumulated time
Integer
0 to 9999
Seconds
-
14
40415
Accumulated time
Exponent
-1 to 21
-
-
15
40716
Clear time
accumulator
command
0 to 1
-
0
(1) On the M6 and M8, setpoint #19 and #20 default to detect voltage sag and voltage swell. See Sag and Swell, page 8-13