Product Description 2-11

Table 2.4 RS-232 Optional Communications (catalog numbers ending in -232)

LED

LED Color

LED State and Communications
Condition

F1

Off

Not Used

RS-232 RX

Off

The RS-232 bus is idle; no active data is
present

Flashing Green

Powermonitor 3000 is receiving data.

RS-232 TX

Off

The Powermonitor 3000 is not transmitting
any data onto the RS-232 bus

Flashing Green

The Powermonitor 3000 is transmitting
data.

Table 2.5 Remote I/O Optional Communications (catalog numbers ending in -RIO)

LED

LED Color

LED State and Communications
Condition

F1

Off

Not Used

F2

Off

Not Used

R I/O

Off

Remote I/O communications has not been
established

Flashing Green

Remote I/O communications has been
established but there are errors

Steady Green

Remote I/O communications has been
established

Table 2.6 DeviceNet Optional Communications (catalog numbers ending in -DNT)

LED

LED Color

LED State and Communications
Condition

F1

Off

Not Used

F2

Off

Not Used

Network Status

Off

Power is off or the Powermonitor 3000 is
not online

Flashing Green

Network status is OK, no connections
established

Steady Green

Network status is OK, connections
established

Flashing Red

Recoverable communications failure; port is
restarting

Steady Red

Non-recoverable communications error;
check wiring and configuration parameters

Powermonitor 3000

F1

RX

TX

}

RS-232

Powermonitor 3000

wermonitor 3000

F1

F2

R I/O

Powermonitor 3000

F1

F2

NETWORK