Publication 1404-UM001D-EN-E - October 2004

A-66 Powermonitor 3000 Data Tables

Table A.55 Time of Use Register Configuration

CSP File No.

N55

Remote I/O BT

49

CIP Assy. Inst.

70 (Write), 71 (Read)

No. of Elements

10

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Default

Comment

0

42201

Password

-1 to 9999

0

Required for configuration, -1 for readback select,
Returns -1

1

42202

Record to read back

0 to 12

0

Refer to Configuring the Time-of-Use Log on page 7-17

2

42203

Reserved

0

0

3

42204

Write command

0 to 1

0

4

42205

Log day

1 to 31

31

5

42206

Off peak day

0 to 127

65

6

42207

Mid peak a.m.

0 to 4095

1792

7

42208

Mid peak p.m.

120

8

42209

Peak a.m.

2048

9

42210

Peak p.m.

7

Table A.56 Time of Use Records – Real Energy and Demand

CSP File No.

F56

Remote I/O BT

51

CIP Assy. Inst.

72

No. of Elements

12

User Configurable No
Data Type

Floating point

Data Access

Read only

PM3000 Type

All