Powermonitor 3000 Data Tables A-65

Table A.53 Controller Command

CSP File No.

N53

Remote I/O BT

-

CIP Assy. Inst.

67

No. of Elements

1

User Configurable No

Data Type

Integer

Data Access

Write only

PM3000 Type

Series B Ethernet only

Element
No.

Element name

Range

Default
Value

Comment

0

Controller Command
Bits 0

0 to 32767

0

Refer to Network Demand / Time
Configuration on page 3-29

Table A.54 Daylight Saving Time Configuration

CSP File No.

N54

Remote I/O BT

47

CIP Assy. Inst.

68 (Write), 69 (Read)

No. of Elements

10

User Configurable No
Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Element
No.

Modbus
Address

Element name

Range

Default

Comment

0

42101

Password

-1 to 9999

0

Required for configuration. Returns -1

1

42102

DST Enable

0 to 1

0

0 = Disabled, 1 = Enabled

2

42103

DST Start Month

1 to 12

4

1 = January, 2 = February, etc.

3

42104

DST Start Day

0 to 6

0

0 = Sunday, 1 = Monday, etc.

4

42105

DST Start Day Instance

1 to 5

1

1 = 1st, 2 = 2nd, ... 5 = Last

5

42106

DST Start Hour

0 to 23

2

0 = 12:00 midnight, 1 = 1:00 AM, etc.

6

42107

DST End Month

1 to 12

10

1 = January, 2 = February, etc.

7

42108

DST End Day

0 to 6

0

0 = Sunday, 1 = Monday, etc.

8

42109

DST End Day Instance

1 to 5

5

1 = 1st, 2 = 2nd, ... 5 = Last

9

43110

DST End Hour

0 to 23

2

0 = 12:00 midnight, 1 = 1:00 AM, etc.