Chapter 3
Product Commissioning
Table 21 - Bulletin 290E/291E Produced Assembly
Status Tag Explanation
Device Input Status Tags
Tag Description/Use
Fault
Communication fault between PLC and device (all 1s = fault, all 0s = normal)
TripPresent
Fault exists within unit
WarningPresent
Warning of potential fault
RunningForward
Motor commanded to run forward
RunningReverse
Motor commanded to run reverse
Ready
Control and 3-phase power present
CurrentFlowing
Current is passing to motor
DeviceLogixEnabled
DeviceLogix is enabled
KeypadAuto
HOA is in Auto mode
KeypadOff
HOA is in Off mode
KeypadHand
HOA is in Hand mode
DisconnectClosed
Disconnect is closed
Pt00Data
User-configured I/O status
Pt01Data
User-configured I/O status
Pt02Data
User-configured I/O status
Pt03Data
User-configured I/O status
Pt04Data
ASLT_DEMO:I.Pt04Data
Pt05Data
User-configured I/O status
Pt00DeviceOut
DeviceLogix network output status
Pt01DeviceOut
DeviceLogix network output status
Pt02DeviceOut
DeviceLogix network output status
Pt03DeviceOut
DeviceLogix network output status
Pt04DeviceOut
DeviceLogix network output status
Pt05DeviceOut
DeviceLogix network output status
Pt06DeviceOut
DeviceLogix network output status
Pt07DeviceOut
DeviceLogix network output status
Pt08DeviceOut
DeviceLogix network output status
Pt09DeviceOut
DeviceLogix network output status
Pt10DeviceOut
DeviceLogix network output status
Pt11DeviceOut
DeviceLogix network output status
Pt12DeviceOut
DeviceLogix network output status
Pt13DeviceOut
DeviceLogix network output status
Pt14DeviceOut
DeviceLogix network output status
Pt15DeviceOut
DeviceLogix network output status
Int00DeviceOut
DeviceLogix network analog output
L1Current
Phase A current
L2Current
Phase B current
L3Current
Phase C current
AvgCurrent
Average phase A, B, and C current
PercentTCU
Overload percentage thermal utilization (100% = overload trip)
SwitchedVoltageLevel
Switched control power voltage — Parameter 11